Technical Data | HPC-500K-TT | HPC-630K-TT |
DC Input | ||
Maximum Input Voltage | 850 V | |
Voltage Range | 500~850 V | 630~850 V |
AC Output (On-Grid) | ||
Rated Power | 500 kW | 630 kW |
Maximum Output Power | 550 kVA | 693 kVA |
Maximum Output Current | 794 A | 1000 A |
Rated Grid Voltage | 400 V | |
Rated Grid Frequency | 50/60 Hz (45~55 / 55~65) | |
Power Factor (Rated Power) | >0.99 | |
THDi (Rated Power) | <3% | |
Power Factor | 1 (0.8 leading~0.8 lagging) | |
Output System | 3PH, N, PE | |
AC Output (Off-Grid) | ||
Rated Output Power | 500 kW | 630 kW |
Maximum Output Power | 550 kVA | 693 kVA |
Rated Output Voltage | 400 V | |
Overload Capacity | 110% Long Run | |
Rated Output Frequency | 50/60 Hz | |
THDu (Linear Load) | <3% | |
Unbalanced Load Capacity | 100% | |
General Data | ||
Maximum Efficiency | 97.6% | |
Protection | DC Overvoltage Protection, DC Short Circuit Protection, AC Overvoltage Protection, Polarity Reverse Protection, Module Temperature Protection | |
Ingress Protection Rating | IP20 | |
Isolation Transformer | Yes | |
Temperature Range | -30~55ºC | |
Cooling Method | Forced Air Cooling | |
Relative Humidity | 0~95%, Non-condensing | |
Altitude | ≤5000 m (>3000 m Derating) | |
Display | Touch Screen | |
Communication | Ethernet, RS485 | |
BMS Communication | RS485, CAN | |
Communication Protocol | Modbus, IEC104 | |
Standby Consumption | <50 W | |
Weight | 3000 kg | 3200 kg |
Dimensions (WxDxH) | 2100x1050x2260 mm | 2400x1050x2260 mm |
Commercial
PCS (Power Conversion System) (Built-in Transformer, 500kW / 630kW)
- Power frequency topology, industrial design
- AC and DC dual power backup, ensure the power supply of the control system
- High power density, maximum efficiency up to 97.6%
- High-performance DSP, optimized control circuit design, better performance
- DC wide voltage input, compatible with different batteries
- Functions of grid connected charging and discharging and off-grid independent inverter
- Reactive power and active power are adjustable
- Supports diesel generator access, switching between on-grid and off-grid (optional)
- Cold start with load, three-phase 100% unbalanced load, strong load adaptability
- Friendly grid adaptability, accept power grid dispatch
- Intelligent management control strategy, multiple working modes, online or remote switching